Your browser has JavaScript turned off.
You must turn it on to proceed.










NORS -- CSRIC Best Practices Result

CSRIC Best Practices Result

Detailed Information for the Best Practice: 9-9-0658

Number 9-9-0658
Priority Critical
Description Network Operators, Service Providers, Property Managers and Public Safety should ensure generator life support systems (e.g., radiator fan, oil cooler fan, water transfer pumps, fuel pumps, engine start battery chargers) are on the essential Alternating Current (AC) buss of the generator they serve.
Network Type(s) Cable; Internet/Data; Satellite; Wireless; Wireline
Industry Role(s) Service Provider; Network Operator; Property Manager
Keyword(s) Buildings;Business Continuity;Emergency Preparedness;Pandemic;Power;Procedures;